Our website uses cookies. Accept
In English Suomeksi

2012

Panel meter

Manufacturer

Nokeval

Article

93245

The display has a 10-point linearization for inputs, which enables adjustments when, for example, measuring liquid-level in round-bottom containers with a pressure sensor. Optional 2-6 alarm relays, output 4-20 mA or with RS485 serial card.


Available in two panel meter model options:
2012-24VDC Panel meter for process inputs, 24 VDC power supply
2012-230VAC Panel meter for process inputs, 230 VAC power supply


The panel meter replaces the earlier 2011 model with compatible connections.

Load manuals (pdf)

Input details

linearity

±2 mV voltage input, ±3μA current input


inputs

mA, Ohm, V


input resistance

voltage input: 1.1 MΩ, current input: 80 Ω


supply for transmitter

24 VDC, max. 150 mA


drift

±100 ppm/°C


input channels

1


accuracy

+-8 μA current input, +-5 mV voltage input


special functions

Display hold, reset of alarms or display taring using external contact

Display details

display color

red


number of digits

6


indicator lights

alarm levels 1 and 2


display

7 segment LED


digit size

14.5 mm

Power supply

power consumption

2,5 VA


current consumption

24 VDC: 70...110 mA depending on the digit count


supply voltage

24 VDC: 12...32 VDC / 24 VAC, 230 VAC: 85-260 V AC/DC

General information

weight

240 g


protection class

IP65 (front panel with a rubber gasket provided)


dimensions

96 x 48 x115 mm (WHD)


installation

panel


minimum ambient temperature

-10 °C


case material

plastic, black


maximum ambient temperature

60°C

Versatile panel meter for 2012 process inputs, mA/V and potentiometer.